As an ENERGY STAR
®
Partner, U.S. Boiler Company has determined that this boiler meets the ENERGY
STAR
®
guidelines for energy efciency established by the United States Environmental Protection Agency (EPA).
103780-03 - 9/12
INSTALLATION, OPERATING AND
SERVICE INSTRUCTIONS FOR
ES2
ENHANCED SERIES 2
Gas - Fired Boiler
9700609
Price - $5.00
For service or repairs to boiler, call your heating contractor. When seeking information on boiler, provide
Boiler Model Number and Serial Number as shown on Rating Label.
Boiler Model Number
ES2__B
Boiler Serial Number Installation Date
Heating Contractor Phone Number
Address
Zobrazit stránku 0
1 2 3 4 5 6 ... 55 56

Shrnutí obsahu

Strany 1 - SERVICE INSTRUCTIONS FOR

As an ENERGY STAR® Partner, U.S. Boiler Company has determined that this boiler meets the ENERGY STAR® guidelines for energy efciency established

Strany 2 - WARNINGS FOR THE INSTALLER

102. Screw the water supply manifold into the boiler outlet tapping “O.”3. Orient the manifold with the relief valve on top.4. Screw the relief val

Strany 3 - What's in the crate?

117. Screw an installer-supplied 1¼” pipe or nipple into the water return tapping “R”.8. Screw the supplied drain valve into tapping “D”.6. CONNECT

Strany 4 - SPECIFICATIONS

12 DISCONNECT ELECTRICAL POWER to the boiler and heating system before servicing. Positively assure that no voltage is present. Lock ele

Strany 5 - SPECIFICATIONS (continued)

13Using Intelligent Hydronic Control Display8. PROGRAM THE CONTROLSViewing the Operating Mode OptionsIn operating mode the user may view (but not cha

Strany 6 - BOILER QUICK-START

14Unit DisplayORSample Display1 sec1 sec1 sec Please note that in operating mode to hold the display on the value the user can press and hold either t

Strany 7 - 1. UNPACK THE CRATE

15Circulator Pre-purge time has a factory setting of 2 minutes and is eld adjustable between 2 and 20 minutes. When reset card is installed, pre-pur

Strany 8 - CAUTION

168. PROGRAM THE CONTROLS (continued)b. When dh_ is set equal to Second Heating Zone (tt2) When there is no IWH the “DHW Circulator” output may b

Strany 9 - 4. CONNECT VENTING

1710-b10. PERFORM STARTUP CHECKS AND ADJUSTMENTS FAILURE TO PERFORM THESE CHECKS of the boiler's combustion and safety systems may

Strany 10 - 5. CONNECT GAS PIPING

18ANNUAL MAINTENANCE CHECKLIST WARNINGSTHE BOILER CONTAINS REFRACTORY CERAMIC FIBER, a possible human carcinogen Use a NIOSH approved respirator whe

Strany 11 - Item Description Part Number

19TROUBLESHOOTINGBefore troubleshooting The following pages contain trouble shooting tables for use in diagnosing control problems. When using thes

Strany 12 - 7. CONNECT ELECTRICAL WIRING

2FOLLOW ALL INSTRUCTIONS and warnings printed in this manual and posted on the boiler.INSPECT THE BOILER ANNUALLY. To keep your boiler safe and efcie

Strany 13 - 8. PROGRAM THE CONTROLS

20TROUBLESHOOTING (continued)Use Control Display ERR (error) Number To Direct TroubleShooting Efforts If the control detects an error it will ash “E

Strany 14 - Unit Display

21Use STA (status) Number To Guide TroubleShooting The control will ash “STA” followed by a number. Use this number to identify the boiler problem

Strany 15

22TROUBLESHOOTING (continued)6. Circulator is On, Damper is Open but Boiler Fails to Start Display / Status DescriptionSTA 10Retry / RecycleDelayThe

Strany 16

23TROUBLESHOOTING (continued)Display / StatusRecommended Corrective ActionStA 10Retry / Recycle DelayStA 13Soft Lockout1. No Spark a. Can you he

Strany 17

24TROUBLESHOOTING (continued)If Control Shows Status Code “STA 15": The control is “Waiting for Limit to Close” and the display on the IQ Optio

Strany 18 - WARNINGS

25Key No.Description[Quantity] Part Number ES23 ES24 ES25 ES26 ES27 ES28 ES291A Block Assembly 102287-03 102287-04 102287-05 102287-06 102287-07 10228

Strany 19 - TROUBLESHOOTING

26REPAIR PARTS LIST (continued)Key No.Description[Quantity] Part Number ES23 ES24 ES25 ES26 ES27 ES28 ES292A Base Wrapper 71807031 71807041 71807051 7

Strany 20 - TROUBLESHOOTING (continued)

27REPAIR PARTS LIST (continued)Key No.Description[Quantity] Part Number ES23 ES24 ES25 ES26 ES27 ES28 ES293AGas Valve (Natural Gas), Honeywell VR8204P

Strany 21 - Display / Status

28REPAIR PARTS LIST (continued)Key No.Description[Quantity] Part Number ES23 ES24 ES25 ES26 ES27 ES28 ES294A Control 103660-014B IQ Option Panel 10229

Strany 22

29Key No.Description[Quantity] Part Number ES23 ES24 ES25 ES26 ES27 ES28 ES295A Jacket Left Side Panel 102566-015B Jacket Right Side Panel 102567-015C

Strany 23

3Congratulations on your purchase of a new ES2™ boiler—designed and constructed to provide you with years of reliable service. • ENERGY STAR™ effici

Strany 24

30REPAIR PARTS LIST (continued)Key No.Description[Quantity] Part Number ES23 ES24 ES25 ES26 ES27 ES28 ES296A Supply Water Manifold 806070016B Temperat

Strany 25 - REPAIR PARTS LIST

31INTERNAL WIRING Figure IW-1: Wiring Diagram

Strany 26 - REPAIR PARTS LIST (continued)

32INTERNAL WIRING (continued)Figure IW-2: Wiring Schematic

Strany 27

33Figure IW-3: Multiple Zone System with Zone CirculatorsINTERNAL WIRING (continued)Figure IW-4: Multiple Zone System with Zone Valves

Strany 28

34Figure IW-5: Multiple Zone System with Zone Circulator PanelINTERNAL WIRING (continued)T STAT 1VALVE 1T STAT 2VALVE 2T STAT 3OFFONZONE 4 PRIORITYTA

Strany 29

35APPENDIX A – COMBUSTION AIR PROVIDE ENOUGH AIR to ventilate the boiler room, dilute the ue gases, and sustain combustion. Ignition fail

Strany 30

36APPENDIX B – VENTING VENT THIS BOILER according to the instructions. Failure to do so may cause products of combustion to enter the buil

Strany 31 - INTERNAL WIRING

37 Au moment du retrait d’une chaudière existante, les mesures suivantes doivent être prises pour chaque appareil toujours raccordé au système d’eva

Strany 32 - INTERNAL WIRING (continued)

38APPENDIX B1 – ATMOSPHERIC VENTINGFigure B-1: Typical Atmospheric Vent Installation GENERAL WARNINGS FOR ATMOSPHERIC VENTING SYSTEMSUSE ATMOSPHERI

Strany 33

39N’ÉVACUEZ LES PRODUITS DE LA COMBUSTION DU GAZ DANS L’ATMOSPHÈRE que dans le cas de chaudières approuvées pour cela comme le stipule la section Spéc

Strany 34

4 ES2 SeriesBoiler ModelInput (MBH) DOE Heating Capacity (MBH) Net AHRI Rating (MBH) AFUE (%)ES23 70 59 51 85ES24 105

Strany 35 - APPENDIX A – COMBUSTION AIR

40APPENDIX C – GAS PIPING ASSURE GAS PIPING IS LEAK FREE AND OF PROPER SIZE and type for the connected load. SHUT OFF MAIN GAS SUPPLY

Strany 36 - APPENDIX B – VENTING

415. Bond all above-ground gas piping to a grounding electrode and ensure the piping is electrically continuous. DO NOT USE GAS PIPING AS A

Strany 37

423. Overpressure(1) Install a properly sized expansion tank. (2) Do not exceed the boiler’s specic requirements for maximum allowable working

Strany 38

43APPENDIX D – System Piping (continued)Figure D-W2: Recommended Water Piping for Zone Valve Zoned Heating Systems

Strany 39

44APPENDIX D – System Piping (continued)Figure D-W3: Recommended Water Piping for Circulator Zoned Heating Systems

Strany 40 - APPENDIX C – GAS PIPING

45APPENDIX E – FILLING THE SYSTEM AND CHECKING FOR LEAKSFill entire heating system with water and vent air from system. Use the following procedure o

Strany 41 - APPENDIX D – SYSTEM PIPING

46APPENDIX F – ADJUSTING GAS INPUT RATECheck Manifold Pressure:1. Note the rated manifold gas pressure listed on the boiler’s rating label.2. Connec

Strany 42

47APPENDIX G – CHECKING DRAFT AND COMBUSTIONCHECK DRAFT (GAS BOILERS WITH DRAFT HOODS)1. Insofar as is practical, close all doors and windows in the

Strany 43

48APPENDIX H – OPERATIONBoiler Sequence of OperationNORMAL OPERATION1. The ES2 Boilers are equipped with an Intelligent Hydronic Control (control).

Strany 44

49APPENDIX I – IQ CONTROL SYSTEMIQ Control System Overview The “IQ Control System” consists of a control and an IQ Option Panel with optional “plug in

Strany 45

5Figure S-1: Minimum Clearances to Combustibles and Alcove DimensionsSPECIFICATIONS (continued)

Strany 46

50APPENDIX I – IQ Control System (continued)IQ Outdoor Reset Option Card Kit: P/N 102723-01 Installing the IQ Outdoor Reset Option Card is the simpl

Strany 47

51APPENDIX I – IQ Control System (continued)IQ High Limit Option Cards add auxiliary temperature limit-rated controls to ES2 Boilers. High Limit Opti

Strany 48 - APPENDIX H – OPERATION

52APPENDIX I – IQ Control System (continued)Part Number Item Description102723-01Outside Reset IQ Option Card, Domestic Hot Water Priority, for use wi

Strany 49

53NOTES

Strany 50

54NOTES

Strany 51

55NOTES

Strany 52 - Additional Information List

56U.S. Boiler Company, Inc.P.O. Box 3020Lancaster, PA 176041-888-432-8887www.usboiler.net

Strany 53

6Installation: 1. Unpack the crate ... 7 2. Position t

Strany 54

7 THE BOILER IS TOP-HEAVY. Do not allow it to tip over.1. Remove the sleeve. 2. Remove the contents from the skid, except the boiler.

Strany 55

82. POSITION THE BOILER WARNINGS1. Slide the boiler into desired location.2. Meet the minimum clearances to combustible construction per the Speci

Strany 56 - 1-888-432-8887

94-a3. PROVIDE COMBUSTION AIR INSUFFICIENT COMBUSTION AIR SUPPLY may result in the production and release of deadly carbon monoxide (CO