RTC Kit Selection Chart
(1)
SELECT BOILER SIZE BASED ON ∆ T
(4)
VALVE
SIZE
(1) (2)
BASIC
RTC KIT
PART #
RTC KIT w/
OUTDOOR RESET
PART #
APPROXIMATE
SHIPPING
WEIGHT20° ∆ T 40° ∆ T
— V903 1.0 NPT" 60160851 60160861 17
— V904 1.25 NPT" 60160852 60160862 17
V903
V904
V905, V906
V1104, V1105
1.5 NPT" 60160853 60160863 20
V905
V1104
V907, V908, V909
V1106, V1107, V1108
2.0 NPT" 60160854 60160864 24
V906, V907, V908
V1105, V1106
V910, V911, V912
V1109, V1110, V1111
2.5" FLG
(3)
60160855 60160865 47
V909, V910, V911
V1107, V1108, V1109
V1112, V1113, V1114
V1115, V1116, V1117
2.5" FLG
(3)
60160856 60160866 47
V912
V1110, V1111, V1112, V1113
V1118 V1119, V1120
V1121, V1122, V1123
3.0" FLG 60160857 60160867 55
V1114, V1115
V1116, V1117, V1118
— 4.0" FLG 60160858 60160868 80
V1119, V1120
V1121, V1122, V1123
— 5.0" FLG 60160859 60160869 93
1. Requires addition of a boiler circulator, to be provided by installer. See back page for circulator selection.
2. Pipe size varies on application – Refer to I & O Manual for details.
3. The 2.5” valves have diferent Cv values. Refer to the I & O Manual for details.
4. RTC can be used on other Burnham Commercial products. Consult factory for application.
RTC Return Temperature Control Specification
1. The Burnham RTC Return Temperature Control is a CSA certified microprocessor based control that will control boiler
return water temperature to prevent thermal shock and flue gas condensation.
2. The control shall have a 120V power supply with a built in 24V transformer to power a floating action type actuator.
3. The control shall provide a 24V floating output signal to modulate a three-way or a four-way diverting valve based on a
signal from the return temperature sensor mounted in the return piping to the boiler.
4. The control shall have an LCD display to view system status and operating information.
5. The control shall have a non-volatile memory to monitor supply and return water temperatures and boiler run times.
6. The control shall have a boiler minimum setting of 135°F and shall not be programmable any lower than 135°F.
7. The control shall have a warm weather shut down feature, a heat demand input, boiler contact and pump contact.
8. The control must receive a heat demand before it can operate. When the demand is removed, the diverting valve shall
fully close before it is allowed to respond to the new heat demand.
9. The control shall have a test sequence to ensure proper component operation, an adjustable pump post purge of zero to
240 seconds, exercising of pump and diverting valve, error messages when it detects a malfunction and an adjustable
actuator motor speed setting of 30 to 230 seconds.
10. The control shall have the ability to operate with an outdoor reset function. This requires the use of a mixed water sensor
and an outdoor air sensor.