A5. 4-way RTC in Primary/Secondary - Heating Only/No DHW; with/without Outdoor Reset (Mechanical)
120 V (ac)
24 V (ac)
Class II
Transformer
RTC
Outdoor Sensor
(S3) 070
P1
Boiler Return
Sensor
(S1) 071
M
V2
P2
S2
4D Max
M
Z3
P2
V1
M1
C1
S2
M
Z2
M
Z1
C1 = Diverting Valve Actuating Motor
M1 = By-Pass Mix Point
P1 = Boiler Circulator
P2 = System Pump (runs on call for heat)
S1 = Boiler Return Sensor
S2 = Mix Supply Sensor 071 (Required
for Reset Control)
S3 = Outdoor Sensor 070 (Required
for Reset Control)
V1 = 4-Way Diverting Valve
V2 = Ball Valve, Balancing Valve
Z1...Z3 = Zones
NOTES:
1) Install the boiler as indicated above for systems where return temperatures may be less than 135F and heating
application only.
2) The Outdoor Sensor (S3) and the Mix Supply Sensor (S2) are required when the Outdoor Reset feature is selected. The
mix sensor must be installed 10 pipe diameters downstream of the system pump, in the primary loop. The mix sensor must be
secured to the surface of the pipe using a wire tie or similar device.
3) The by-pass piping, diverting valve and boiler circulator must be sized using the sizing charts found in Appendix B.
4) Closely spaced tees must connect the branch to the larger header. The Tee centerlines must be no greater than 4 times the
larger header pipe diameter.
5) The diverting valve, V1, must be no greater than 11 linear feet of pipe from the Return Sensor, S1.
6) There shall be a MINIMUM of 4 linear feet of pipe between the By-pass Mix Point, M1, and the Return Sensor, S1.
7) The balancing valve in the boiler return line, V2, may be necessary in low head by-pass loop applications.
8) Expansion tanks, air scoops and other components left out for clarity.
9) Observe all applicable plumbing and electrical codes.
This diagram is for reference only. The installer or designer is responsible for the proper selection and design of the